Cleaning Protocol
Before washing, several safety measures must be taken:
- Wrap the humidity sensor, on the right side of the coil, in plastic wrap
- Open the electrical panel and turn the main circuit breaker OFF
- Cover the electrical panel with plastic wrap, so water cannot penetrate during washing
Cleaning the coil:
ACE ECO-KLEEN (EKC) must be diluted 1:4 with water (4 liters of water for every liter of cleaning fluid)
- Spray the coil with a low-pressure sprayer
- Leave the material on the coil for 3-7 minutes, then rinse with water
- After washing – wait 30 minutes, then remove the plastic wrap from the sensor and electrical panel, and turn the unit ON
- If there are crooked aluminum fins on the coil, use the fin straightener and straighten them