The following troubleshooting guide offers solutions to common errors and faults. If you do not find a solution within this guide, please contact our technical support team.
General / Initial Troubleshooting

Make sure the fans are running, and there are no objects obstructing the airflow.

  1. Open the electrical cabinet door to access the electrical panel
  2. Make sure all circuit breakers are set to ON
  3. Ensure the mode selector is set to LOCAL
  4. Check if the red general fault light is on
  5. Press RESET and wait for the unit to begin operation
  6. If the unit does not function properly, follow the following instructions:
Fan Fault
  1. Open the electrical cabinet door to access the electrical panel
  2. Is the red general fault light on?
  3. Make sure all switches are set to ON
  4. If so, look towards the row of relays to the left of the red general fault light, to find the RTMA relay
  5. Does the RTMA relay display a light on the bottom left? If not, there is a fan fault
  6. Press RESET, wait a few minutes, and check the RTMA relay again
  7. If pressing RESET hasn’t solved the issue, contact our technical support team
Compressor Fault
  1. Open the electrical cabinet door to access the electrical panel
  2. Is the red general fault light on?
  3. If so, look towards the row of relays to the left of the red general fault light, to find the RCA relay
  4. Does the RCA relay display a light on the bottom left? If it does, there is a compressor fault
  5. On the right side of the electrical panel, you’ll find “O.L 31 OL 3.2”. Beneath each is a blue button
  6. Press both blue buttons
  7. If the unit hasn’t begun operation, approach the unit’s side panel (to your left) and open the service door
  8. Press the RESET button, to the right of the “High Pressure” sign, and wait for the compressor to begin operation
  9. If the unit hasn’t begun operation, press the RESET button, located to the right of the “Oil Pressure” sign, and wait for the compressor to begin operation
  10. Return to the electrical panel, and press the main RESET button
  11. If the compressor stops after a few minutes, repeat the previous steps (6-9)
  12. If the issue persists after 2-3 attempts, contact our technical support team
  13. Note which button solved the fault, for future reference
Controller Fault
  1. Open the electrical cabinet door to access the electrical panel
  2. Make sure all switches are set to ON
  3. Locate the black temperature controller display in the back
  4. Does the controller monitor display the temperature?
  5. If there is no image on the display, contact our technical support team
Sensor Fault
  1. Open the electrical cabinet door to access the electrical panel
  2. Make sure all switches are set to ON
  3. Locate the black temperature controller display in the back
  4. If the display shows E01, there is a sensor fault
  5. Turn the main power switch OFF
  6. Identify the red electrical clamps, numbered 50-56
  7. Tighten all cables and ensure they are properly connected, both on the top and bottom
  8. Turn the main power switch ON
  9. If the display still shows E01, press RESET
  10. If the issue persists, contact our technical support team
Lack of Gas
  1. Open the electrical cabinet door to access the electrical panel
  2. Is the red general fault light on?
  3. If so, look towards the row of relays to the left of the red general fault light, to find the RB relay
  4. Does the RB relay display a light on the bottom left? If it does, the unit is lacking gas
  5. Switch mode selector to 0
  6. Press RESET and switch mode selector to LOCAL
  7. Wait a few minutes, and check the RB relay again
  8. If the green light appears again, contact our technical support team
Phase Loss Relay Fault
  1. Open the electrical cabinet door to access the electrical panel
  2. Is the red general fault light on?
  3. If so, look towards the row of relays to the left of the red general fault light, to find the RNVR relay
  4. Does the RNVR relay display a light? If not, there is a problem with the order of phase connections
  5. Press RESET and check if the issue persists
  6. If the light appears again, contact our technical support team
Ice Formation on Unit

Ice formation on the evaporator coil is indicative of one of two issues:

  1. Lack of gas – refer to Lack of Gas
  2. Low environmental temperature – ensure the environmental temperature is within DryGair’s operational limits