The following troubleshooting guide offers solutions to common errors and faults. If you do not find a solution within this guide, please contact our technical support team.
General / Initial Troubleshooting
Make sure the fans are running, and there are no objects obstructing the airflow.
- Open the electrical cabinet door to access the electrical panel
- Make sure all circuit breakers are set to ON
- Ensure the mode selector is set to LOCAL
- Check if the red general fault light is on
- Press RESET and wait for the unit to begin operation
- If the unit does not function properly, follow the following instructions:
Fan Fault
- Open the electrical cabinet door to access the electrical panel
- Is the red general fault light on?
- Make sure all switches are set to ON
- If so, look towards the row of relays to the left of the red general fault light, to find the RTMA relay
- Does the RTMA relay display a light on the bottom left? If not, there is a fan fault
- Press RESET, wait a few minutes, and check the RTMA relay again
- If pressing RESET hasn’t solved the issue, contact our technical support team
Compressor Fault
- Open the electrical cabinet door to access the electrical panel
- Is the red general fault light on?
- If so, look towards the row of relays to the left of the red general fault light, to find the RCA relay
- Does the RCA relay display a light on the bottom left? If it does, there is a compressor fault
- On the right side of the electrical panel, you’ll find “O.L 31 OL 3.2”. Beneath each is a blue button
- Press both blue buttons
- If the unit hasn’t begun operation, approach the unit’s side panel (to your left) and open the service door
- Press the RESET button, to the right of the “High Pressure” sign, and wait for the compressor to begin operation
- If the unit hasn’t begun operation, press the RESET button, located to the right of the “Oil Pressure” sign, and wait for the compressor to begin operation
- Return to the electrical panel, and press the main RESET button
- If the compressor stops after a few minutes, repeat the previous steps (6-9)
- If the issue persists after 2-3 attempts, contact our technical support team
- Note which button solved the fault, for future reference
Controller Fault
- Open the electrical cabinet door to access the electrical panel
- Make sure all switches are set to ON
- Locate the black temperature controller display in the back
- Does the controller monitor display the temperature?
- If there is no image on the display, contact our technical support team
Sensor Fault
- Open the electrical cabinet door to access the electrical panel
- Make sure all switches are set to ON
- Locate the black temperature controller display in the back
- If the display shows E01, there is a sensor fault
- Turn the main power switch OFF
- Identify the red electrical clamps, numbered 50-56
- Tighten all cables and ensure they are properly connected, both on the top and bottom
- Turn the main power switch ON
- If the display still shows E01, press RESET
- If the issue persists, contact our technical support team
Lack of Gas
- Open the electrical cabinet door to access the electrical panel
- Is the red general fault light on?
- If so, look towards the row of relays to the left of the red general fault light, to find the RB relay
- Does the RB relay display a light on the bottom left? If it does, the unit is lacking gas
- Switch mode selector to 0
- Press RESET and switch mode selector to LOCAL
- Wait a few minutes, and check the RB relay again
- If the green light appears again, contact our technical support team
Phase Loss Relay Fault
- Open the electrical cabinet door to access the electrical panel
- Is the red general fault light on?
- If so, look towards the row of relays to the left of the red general fault light, to find the RNVR relay
- Does the RNVR relay display a light? If not, there is a problem with the order of phase connections
- Press RESET and check if the issue persists
- If the light appears again, contact our technical support team
Ice Formation on Unit
Ice formation on the evaporator coil is indicative of one of two issues:
- Lack of gas – refer to Lack of Gas
- Low environmental temperature – ensure the environmental temperature is within DryGair’s operational limits